Capacity and Dimensions Table

  • If possible, pump down system and lock existing refrigerant in the receiver or condenser. If you cannot secure existing system charge, use your Recovery Unit to save and store the refrigerant charge.

Do not release refrigerant into the atmosphere. You will be liable for heavy fines if you do!

  • Before installing the APR Control make sure your system is clean. If not, or in doubt, a filter strainer must be used to protect the APR Control and isolate and remove the system contaminants. (Particles of dirt can settle on the valve seat of the hot gas bypass valve and prevent it from closing, possibly causing compressor overheating and subsequent system damage.)
  • After you install the APR Control, use standard evacuation procedures and follow the directions listed below. All connections between the system and the APR Control are made in the condensing section. The APR Control may be placed outside the unit housing. The APR Control may be mounted vertical or horizontally.

Note - If you choose to mount the APR Control vertically - the mixed gas discharge from the top of the desuperheating chamber must be UP! Using line valves to isolate the APR Control inlet liquid, hot gas and external equalizer connections, and outlet mixed gas discharge line, is recommended but optional, and not functionally required.

  • All soldering connections to the APR Control should be made with Type 400 6% Silver (205 deg. C) Solder only. Do not hard solder or silver solder APR Control connections to your system. Exceptions can be made where vibration or pulsation is present or where Government specifications call for hard solder or braising.
  • To eliminate damage to the APR Control Valves, use plenty of wet rags or Heat Absorbing Paste on the valves prior to starting, and aim your flame away from the valve bodies.
  • Tee in a line shut-off valve at the compressor hot gas discharge line -- size valve to the APR Control hot gas inlet valve inlet -- where a strainer is supplied, install it in the 5/8î or 7/8î hot gas valve inlet only.
  • Tee in a line shutoff valve at the compressor suction line — size it to the APR Control mixed gas discharge (TOP) outlet, either 5/8î or 7/8î ODF.
  • Tee in line shutoff valve at the liquid line near the condenser coil or receiver outlet. Size this valve to the 3/8î ODF APR Control thermal expansion valve inlet.
  • If your system uses PUMPDOWN or PUMPOUT control, line valve M, the mixed gas line valve must be replaced by a solenoid valve with manual stem for shut off. The coil voltage should be your unit control voltage.
  • Mount the APR Control securely within the condensing unit.
  • Connect hot gas from the line valve to the APR Control hot gas bypass valve inlet G
  • Connect suction from the line valve to the APR Control mixed gas outlet M
  • Connect 3/8 liquid from the line valve to the APR Control thermal expansion valve inlet L
  • External Equalizers must be coupled for one suction line connection only.
  • Thermal expansion valve bulb must be the last APR Control connection and nearest the compressor.
  • Leak test system and evacuate. Before charging system close all APR Control line valves, do not leave
  • APR Control open when charging the system. No additional charge is necessary for the APR Control to operate.
  • APR Control is set at the factory for R-22 /High Temperature application.
  • Thermal Expansion Valve at 57 deg. F (17 deg. superheat)
  • Hot Gas Bypass Valve at 58 psi pressure.
  • Most APR Controls are field adjustable when necessary.

 

return to top of page.


©2002 Rawal Devices. All rights reserved.